Discharge Pressure Check; Outdoor Unit Fan System Check - Daikin FTXG25CVMAW Service Manual

Hide thumbs Also See for FTXG25CVMAW:
Table of Contents

Advertisement

Check
5.1.6

Discharge Pressure Check

Check No.8
Discharge pressure check
5.1.7

Outdoor Unit Fan System Check

Check No.9
108
High
YES
Is the stop valve open?
YES
Is the
connection pipe deformed?
YES
At the heat exchanger and
air filter dirty?
YES
Check the outdoor unit fan system.
Outdoor unit fan running?
YES
Outdoor unit fan
system
functioning.
NO
NO
NO
NO
(With DC Motor)
NO
Fan motor lead wire
connector disconnected?
NO
Go to Check No. 15.
Si04-402A
Replace compessor.
Open the stop valve.
Replace the pipe installed at
the site.
Clean.
Replace the compressor.
(R1443)
YES
Reconnect.
(R2857)
Service Diagnosis