Daikin FUY71FJV1 Installation Manual page 13

Split system
Hide thumbs Also See for FUY71FJV1:
Table of Contents

Advertisement

Elbow (9)
Sealing pad (8)
Sealing pad (8)
Upward
running
pipe
Fig. 28
CAUTION
• Do not twist or bend the drain hose (1), so that exces-
sive force is not applied to it, as this could cause leaks.
PRECAUTIONS FOR UPWARD DRAIN RAISING PIPING
• Install the drain raising pipes at a height of less than
500mm.
• Install the drain raising pipes at a right angle to the
indoor unit. (Refer to Fig. 29)
Fig. 29
CAUTION
If the upward running drain hose leans at a slant, the float
switch will malfunction and water will leak.
English
Clamp (2)
Long
end
Clamp (2)
Drain hose (1)
Sealing pad (8)
Elbow (9)
Clamp (2)
Short end
WRONG
7-2 After piping work is finished, check if drainage
flows smoothly.
• Open the water inlet lid, add approximately 1000cc of
water slowly and check drainage flow. (Refer to Fig. 30)
Inspection opening
Service cover
≥100
Drain pipe
Plastic watering can
(Tube should be about 100mm long.)
Adding water through air discharge outlet
Method of adding water
Fig. 30
[Caution]
Drain piping connections
• Do not connect the drain piping directly to sewage pipes that
smell of ammonia. The ammonia in the sewage might enter
the indoor unit through the drain pipes and corrode the heat
exchanger.
WHEN ELECTRIC WIRING WORK IS FINISHED
• Check drainage flow during Cooling operation, explained
under "TEST OPERATION".
WHEN ELECTRIC WIRING WORK IS NOT FINISHED
CAUTION
• Electrical wiring work should be done by a certified electri-
cian.
• If someone who does not have the proper qualifications per-
forms the work, perform the following after the test run is
complete.
• Remove the control box lid and change the emergency
switch above the PC board assembly of the indoor unit from
"NORM." to "EMERG.". Connect the single-phase power
supply and earth wire to the power supply (50Hz 220-240V)
terminal board and confirm drain operation.
Be sure to change the switch before turning on the power.
(Refer to Fig. 31)
CAUTION
• Clamp solidly to clamp C to make sure no excess pressure
is applied to the wiring connections.
• Be aware that the fan will turn during the operation.
• After confirming drainage, turn off the power and be sure to
change the emergency switch back to "NORM.".
Indoor PC
board
assembly
Single phase power supply
NORM. EMERG.
1 2 3
Emergency switch
(Normal, Emergency)
(FUQ model)
Fig. 31
Service drain outlet
(with rubber plug).
(Use this outlet to drain water
from the drain pan.)
≥100
Adding water from inspection opening
Power supply terminal board
Tab
Clamp C
Clamp C
1 2 3
Power
supply
terminal
board
(Other models)
10