Outdoor Unit - Lennox 14HPX-018 Installation Instructions Manual

14hpx series
Hide thumbs Also See for 14HPX-018:
Table of Contents

Advertisement

Table 14. Defrost
Control
Board
Diagnostic
LEDs
DS2
DS1
Green
Red
Condition/Code
Possible
Cause(s)
Solution
OFF
OFF
Power problem
No power (24V) to board termi-
1 Check control transformer power (24V).
nals R & C or board failure.
2 If power is available to board and LED(s) do
not light, replace board.
Simultaneous
Normal operation
Unit operating normally or in
None required.
SLOW Flash
standby mode.
Alternating
5-minute anti-short cycle
Initial power up, safety trip, end of
None required (Jumper TEST pins to override)
SLOW Flash
delay
room thermostat demand.
Simultaneous
Ambient Sensor Problem
Sensor being detected open or shorted or out of temperature range. Board will re-
FAST Flash
vert to time/temperature
defrost operation. (System will still heat or cool).
Alternating
Coil Sensor Problem
Sensor being detected open or shorted or out of temperature
range. Board will not
FAST Flash
perform demand or time/temperature
defrost operation. (System will still heat or
cool).
ON
ON
Circuit Board Failure
Indicates that board has internal component failure. Cycle 24 volt power to board. If
code does not clear, replace board.
FAULT
& LOCKOUT
CODES
(Each fault adds 1 strike to that code's
counter;
5 strikes
per code = LOCKOUT)
OFF
SLOW
Low Pressure Fault
Flash
ON
Low Pressure
LOCKOUT
OFF
High Pressure
Fault
High Pressure LOCKOUT
Discharge Line Tempera-
ture Fault
Discharge Line Tempera-
ture LOCKOUT
Discharge Sensor Fault
Discharge
Sensor
LOCKOUT
OFF
SLOW
Flash
ON
OFF
SLOW
ON
Flash
FAST
ON
Flash
OFF
Fast
Flash
Fast
OFF
Flash
1 Restricted air flow over indoor or
outdoor coil.
2 Improper refrigerant charge in
system.
3 Improper metering device
installed or incorrect operation
of metering device.
4 Incorrect or improper sensor
location or connection to sys-
tem.
1 Remove any blockages or restrictions from
coils and/or fans. Check indoor and outdoor
fan motor for proper current draws.
2 Check system charge using approach
& sub-
cooling temperatures.
3 Check system operating pressures and
compare to unit charging charts.
4 Make sure all pressure switches and sensors
have secure connections to system to prevent
refrigerant leaks or errors in pressure and
temperature measurements.
This code detects shorted sensor or high discharge temperatures.
If the discharge
line temperature
exceeds a temperature of 300°F (148°C) during compressor op-
eration, the board will de-energize the compressor contactor output (and the defrost
output if active). The compressor will remain off until the discharge temperature has
dropped below 225°F (107°C).
The board detects open sensor or out of temperature sensor range. This fault is
detected by allowing the unit to run for 90 seconds before checking sensor resist-
ance. If the sensor resistance is not within range after 90 seconds, the board will
count one fault. After 5 faults, the board will lockout.
WARNING
I
Maintenance and service must be performed by a qualified
installer or service agency. At the beginning of each cool-
ing season, the system should be checked as follows:
OUTDOOR UNIT
1. Clean and inspect outdoor coil (may be flushed with a
water hose). Ensure power is off before cleaning.
2. Outdoor unit fan motor is pre-lubricated and sealed.
No further lubrication is needed.
3. Visually inspect all connecting lines, joints and coils for
evidence of oil leaks.
4. Check all wiring for loose connections,
5. Check for correct voltage at unit (unit operating),
6. Check amp draw on outdoor fan motor.
Unit nameplate
Actual
7. Inspect drain holes in coil compartment
base and
clean if necessary,
NOTE - If insufficient heating or cooling occurs, the unit
should
be gauged
and refrigerant
charge should
be
checked.
505243
04/08
Page 22

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

14hpx-02414hpx-03614hpx-04214hpx-04814hpx-06014hpx-030

Table of Contents