Room Sealed Balanced Flue System, Negative Pressure; Room Sealed Balanced Flue System, Positive Pressure - Multiple Connection With; 43X , To Trgi 2008) - Viessmann VITODENS Technical Manual

Flue systems for gas condensing boilers
Hide thumbs Also See for VITODENS:
Table of Contents

Advertisement

Design and sizing information for connection on the flue gas side
Room sealed balanced flue system, negative pressure (type C
2
A Effective chimney height relative to the highest positioned
Vitodens
B Ventilation air
C Flue gas
D Room sealed balanced flue system (see below for manufactur-
ers)
E Inspection port
F Pressure compensation aperture
G Check with the flue system manufacturer regarding minimum
clearances.
Room sealed balanced flue system, positive pressure – multiple connection with the Vitodens 200-W, 222-
W and 222-F up to 26 kW (type C
System for balanced flue operation, specifically developed for the
Vitodens 200-W, 222-W and 222-F.
Minimum shaft cross-section:
■ Square: 175 × 175 mm
■ Round: Ø 195 mm.
VIESMANN
28
Room sealed balanced flue systems for negative pressure may, for
example, be obtained from the following manufacturers:
■ eka Edelstahlkamin GmbH
D-95369 Untersteinach
■ Jeremias
Schornstein Systeme
Opfenrieder Str. 12
D-91717 Wassertrüdingen
■ Plewa-Werke GmbH
D-54662 Speicher/Eifel
■ Schiedel GmbH & Co, Hauptverwaltung
Lerchenstrasse 9
D-80995 Munich
■ Wienerberger GmbH
Oldenburger Allee 26
D-30659 Hannover
to TRGI 2008)
43x
Up to 5 Vitodens 200-W, 222-W and 222-F (or 4 Vitodens
3.2 - 19 kW) with the same rated heating output can be connected to
one flue system.
Vitodens with different rated heating output levels can be connected
to the system if the relevant calculations are verified. For this, please
complete the enquiry form on page 30.
(cont.)
, to TRGI 2008)
43x
VITODENS AND VITOSOLAR