CS-ME7DKEG CS-ME10DD3EG / CS-ME10DTEG CS-E15DB4EW
9.1.1.3.
Cooling Operation
9.1.1.3.1.
Thermostat control
• • • • Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5°C.
• • • • Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF
point.
9.1.1.4.
Soft Dry Operation
9.1.1.4.1.
Thermostat control
• • • • Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -2.0°C.
• • • • Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF
point.
9.1.1.5.
Heating Operation
9.1.1.5.1.
Thermostat control
• • • • Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < +2.0°C.
• • • • Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF
point.
40