Horizontal Airflow
1. Automatic horizontal airflow direction can be set using remote control; the vane swings left and right within the angles as
stated below. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as
Figure 1 below.
Heating, with heat exchanger temperature
Cooling, Soft Dry and Ion
2. Manual horizontal airflow direction can be set using remote control; the angles of the vane are as stated below and the
positions of the vane are as Figure 2 above.
Pattern
Airflow Direction
Patterns at Remote
Control
Vane Angle (°)
9.1.1.9.
Quiet operation (Cooling Mode/Cooling area of Dry Mode)
A. Purpose
To provide quiet cooling operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
• • • • When "quiet" button at remote control is pressed.
Quiet LED illuminates.
b. Quiet operation stop condition
1. When one of the following conditions is satisfied, quiet operation stops:
a. Powerful button is pressed.
b. Stop by OFF/ON switch.
c. Timer "off" activates.
d. Quiet button is pressed again.
Operation Mode
1
2
90
65
47
CS-ME7DKEG CS-ME10DD3EG / CS-ME10DTEG CS-E15DB4EW
Vane Angle (°)
A
65 ~ 115
B
90
65 ~ 115
3
4
78
102
5
115