Choice of installation site for side-wall flue termination
Choosing the right location for siting the terminal is critical
to proper functioning of the appliance. As well as the min-
imum clearances (
Fig. 14), the following rules must be
observed:
Concentric side
wall boiler
terminations
or snow line
Fig. 14 Minimum clearances for side wall terminations
1. The termination should not face the prevailing wind
direction.
2. The termination must be installed in such a way that
the flue gases can disperse freely without re-entering
the building.
3. The termination must be at least 2 ft from adjacent
buildings and it must not be possible for the flue gas
to enter adjacent buildings.
4. Where the building adjoins public walkways, the ter-
mination must be located at least 7 ft above ground.
Make sure that freezing condensate does not consti-
tute a hazard.
5. The termination must never be located below building
overhangs, roof eaves, porches, enclosed spaces or
lower parts of the building which could prevent unre-
stricted outflow of the flue gases.
6. The termination must never be located within 3 ft of
inside corners of buildings and never less than 2 ft
from outside corners of buildings.
7. If there is a fan-assisted air intake vent within 10 ft, the
termination must be at least 3 ft above it.
Logano GB125 BE US/CA - Technical specifications are subject to change without prior notice.
.
Concentric side wall boiler terminations
8. The termination must be at least 4 ft below, 1 ft above
or 4 ft horizontally from doors, windows or air inlet
vents.
9. The termination must be at least 1 ft. above ground
and snow line, and protected from falling and accu-
mulating snow, ice, leaves or debris.
10. The termination should be at least 3 ft from any type
of building opening, oil tank filling or venting appara-
tus, and 6 ft from gas meters and similar equipment.
11. The position of the termination should be chosen so
that the last horizontal section of pipe slopes down-
wards to the inside by ¼" per ft. The flue terminal itself
must also be inclined at ¼" per ft to the inside so that
any condensate drains inwards.
5
Boiler installation
.
Concentric side
wall boiler
terminations
6 720 615 063-20.1TL