Mitsubishi Electric DXK09ZJ-S Technical Manual page 11

Inverter wall mounted type residential air-conditioner
Table of Contents

Advertisement

Symbol
A
B
C
D
E
520.6
161
327.3
50.6
D
38.6
12
327.3
89
510
201
800
Content
Service valve connection(gas side)
φ12.7(1/2")(Flare)
Service valve connection(liquid side)
φ6.35(1/4")(Flare)
Pipe/cable draw-out hole
Drain discharge hole
φ20 × 5places
Anchor bolt hole
M10 × 4places
E
17.9
71.2
Terminal block
148.4
33.5
B
A
Notes
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts. An anchor bolt must not
protrude more the 15mm.
(3) Where the unit is subject to strong winds, lay it in such
a direction that the blower outlet faces perpendicularly
to the dominant wind direction.
(4) Leave 1m or more space above the unit.
(5) A wall in front of the blower outlet must not exceed the units height.
(6) The model name label is attached on the right side of the unit.
L2
Intake
Minimum installation space
Examples of
installation
Dimensions
L1
Open
L2
L3
L4
C
L3
Intake
L4
(
Service
)
space
Outlet
L1
I I
I I I
I V
280
280
180
Open
100
75
Open
100
80
80
80
Open
Open
250
250
Unit:mm