CONTROL SYSTEM

10.26 Test Mode

Entering Test Mode
10.26.1
System can enter Test mode in two ways:
x
Automatically when the following conditions exists for 30 minutes
continuously:
o Mode = Cool, Set point = 16, Room temperature = 27±1, Outdoor
temperature = 35±1
Or
o Mode = Heat, Set point = 30, Room temperature = 20±1, Outdoor
temperature = 7±1
x
Manually when entering diagnostics with the following settings:
o Mode = Cool, Set point = 16
o Mode = Heat, Set point = 30
10.27 Unit Operation in Test Mode
In test mode, the unit will operate in fixed settings according to the indoor fan
speed setting:
Indoor Fan Speed Setting
During test mode, protections are disabled, except for stop compressor status.
10.28 Additional Functions and Rules (for DUAL split models)
The DCI SW is fully parametric.
All the model dependent parameters are shown in Blue color and with Italic style
[parameter].
The parameters values are given in the last section of this control logic chapter of
the service manual.
10.29 System Control Concept
All indoor unit related items control remains the same as in single split
applications.
All outdoor units related control logic remains the same as in single split
applications.
The MSMP controller is responsible only for the following control:
x
Setting of system operation mode (cool/heat)
x
Setting the NLOAD for the outdoor units
x
Controlling of the EEV's
x
Dry contacts control
10-16
Low
High
Auto
Revision Y05-01
CONTENT
Unit Setting
Minimum Capacity Setting
Nominal Capacity Setting
Maximum Capacity Setting
Service Manual - PXD DCI