Outdoor Fan Control - Electra PXD 25 DCI Service Manual

Hide thumbs Also See for PXD 25 DCI:
Table of Contents

Advertisement

10.4 Indoor Fan Control
10 Indoor fan speeds are determined for each model. 5 speeds for cool/dry/fan
modes and 5 speeds for heat mode.
When user sets the indoor fan speed to a fixed speed (Low/ Medium/ High), unit
will operate constantly at set speed.
When Auto Fan is selected, indoor unit controller can operate in all speeds. The
actual speed is set according to the cool/heat load.
Turbo Speed
10.4.1
The Turbo speed is activated during the first 30 minutes of unit operation when
auto fan speed is selected and under the following conditions:
x
Difference between set point and actual room temperature is bigger then 3
degrees.
x
Room temperature > 22 for cooling, or < 25 for heating.
10.5 Heating Element Control
Heating element can be started if LOAD > 0.8 * MaximumNLOAD AND Indoor
Coil temperature < 45.
The heating element will be stopped when LOAD < 0.5 * MaximumNLOAD OR if
Indoor Coil temperature > 50.

10.6 Outdoor Fan Control

7 outdoor fan speeds are determined for each model. 3 speeds for cool and dry
modes, and 3 speeds for heat mode, and a very low speed.
Outdoor fan speed is a function of compressor frequency and outdoor air
temperature (OAT).
4 routines for fan control are determined. The control routine selection depends
on operation mode, compressor speed, and outdoor air temperature (OAT) and
heat sink temperature (HST).
Routine
A
B
C
D
Service Manual - PXD DCI
Conditions
Heating with OAT < 15
or
0
Cooling with OAT > 20
C, or HST > 50
or
Faulty OAT
0
Cooling with 20
C > OAT > 7
0
Cooling with 7
C > OAT
Heating with OAT > 15
Revision Y05-01
CONTENT
CONTROL SYSTEM
0
C
0
C
0
C
0
C
10-3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ong 25 dciPxd 50 dciOng 50 dciPxd 35 dciOng 35 dci

Table of Contents