6.3 Pipe length and the elevation
The pipe length and refrigerant amount:
Model
MS9AU-09HRDN1-QRC4W+MOB-09HFN1-QRC
4W
MS9AU-12HRDN1-QRC4W+MOB-12HFN1-QRC
4W
MS9AU-18HRDN1-QRC4W+MOC-18HFN1-QRC
4W
MS9A-24HRDN1-QRC4W+MOF-24HFN1-QRC4
W
Caution:
The capacity test is based on the standard length and the maximum permissive length is based on the
system reliability.
The oil trap should be installed per 5-7 meters.
Pipe size
Standard
length
Gas
Liquid
3/8''
1/4''
(Ф9.52)
(Ф6.35)
1/2''
1/4''
(Ф12.7)
(Ф6.35)
5/8''
3/8''
(Ф15.9)
(Ф9.52)
17
Max.
Max.
Elevation
Length
(m)
B (m)
A (m)
5
8
5
8
5
10
5
10
Additional
refrigerant
(g/m)
20
20
20
20
25
20
25
40