4
Capacity tables
4 - 1
Cooling/Heating capacity tables
FTYN60FV1B+RYN60E3V1B
Cooling
I n door
EWB
EDB
20
(°C)
(°C)
TC
SHC
PI
Heating
50Hz 220-240V
I n door
EDB
-10
(°C)
TC
PI
TC
SYMBOLS
AFR:
Air flow rate
BF:
Bypass factor
EWB:
Entering wet bulb temp.
EDB:
Entering dry bulb temp.
TC:
Total capacity
SHC:
Sensible heating capacity
PI:
Power input
• Outdoor Units • R-410A • RYN-E3V1B
50Hz 220-240V
25
30
TC
SHC
PI
TC
SHC
AFR
Outdoor temperature (°CWB)
-5
0
6
PI
TC
PI
TC
3
(m
/min)
(°C)
(°C)
(kW)
(kW)
(kW)
• Split Sky Air • Outdoor Units
Outdoor temperature (°CDB)
32
PI
TC
SHC
PI
17.4
10
PI
TC
PI
3D051924A
NOTES
1
Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2
shows nominal (rated) capacities and power input.
3
TC, PI and SHC must be calculated by interpolation using the figures
in the above tables. (Figures out of the tables should not be used for
calculation.)
4
About SHC which are not mentioned on the table, please calculate
them with around values in direct proportion.
5
Capacities are based on following conditions:
Corresponding refrigerant piping length:
Level difference:
6
Air flow rate (AFR) and Bypass factor (BF) are taburated above.
AFR
16.2
BF
0.29
35
40
TC
SHC
PI
TC
SHC
7.5 m
0 m
3
1
PI
4
8