R410A TECHNICAL MANUAL Split Unit Air Conditioner Wall Mounted J Series FTN-J, FTYN-J series — Cooling only & Heatpump [50Hz] — TM-5WM-J-ST-A2...
Nomenclature Nomenclature Indoor FT(Y) N 25 J X V1 Power Supply V1: 1 phase 50 Hz 220-240V Production X: OYLM Product Series J: J Series F: F Series Capacity 25: 2500 Watt Refrigerant R410A Model FT: Wall Mounted (Cooling Only) FTY: Wall Mounted (Heatpump) Outdoor R(Y) N 25 CJ X V1...
Application Information Application Information Operating Range Ensure the operating temperature is in allowable range. Cooling Outdoor DB (°C) The use of your air conditioner outside the range of working temperature and humidity can result in serious failure. Indoor WB (°C) Heating Outdoor WB (°C)
Application Information Installation Guideline Sharp edges and coil surfaces are potential injury hazard. Avoid from contact with them. Installation Diagram Indoor unit Caulk pipe hole Cut thermal insulation pipe 30mm or more from ceiling gap with putty. to an appropriate length and wrap it with tape, making Front panel sure that no gap is left in the...
Application Information Cable Size FTN25JXV1 FTN35JXV1 Model Unit RN25CJXV1 RN25FXV1 RN35CJXV1 RN35FXV1 Power supply cable size Number of wire Interconnection cable size Number of wire Recommended fuse FTN50JXV1 FTN60JXV1 FTN80FXV1 Model Unit RN50CJXV1 RN60CJXV1 RR71CXV1 RR71CXY1 Power supply cable size...
fl ow increases, thus lowering the cooling capacity, and as the result the compressor may become defective. Always choose the shortest path and follow the recommendation as tabulated below: Indoor Unit Outdoor Unit Cooling Only Model Indoor FTN25JXV1 FTN25JXV1 FTN35JXV1 FTN35JXV1 Model Outdoor RN25CJXV1...
• The refrigerant gas is charged in the outdoor unit and, if the piping length is 7.6m, additional charge of the refrigerant after vacuuming is not necessary. • When the piping length is more than 7.6m, additional refrigerant charge (g) per additional 1m length as tabulated: R410A – Cooling Only Indoor FTN25JXV1 FTN25JXV1 FTN35JXV1 FTN35JXV1 Model Outdoor...
16°C WB. - 25°C is located between 24°C & 27°C Example: for 19°C WB. Model: FTN25JXV1 – RN25CJXV1 - Thus, Interpolation needs to be applied. Indoor Condition: 25°C DB, 17°C WB 2. Refer to the Indoor WB column, Outdoor Condition: 37°C DB - 17°C is located between 16°C &...
Page 24
Performance Data (b) Indoor Condition: 25°C DB, 16°C WB By Interpolation Method Outdoor Condition: 35°C DB 25°C – 24°C – 3.51kW Outdoor temperature 27°C – 24°C 3.52kW – 3.51kW 35°C x = 3.51kW Similarly, = 2.71kW 3.51 2.57 1.29 = 1.29kW 3.52...
Outline & Dimension Outdoor Unit Model: R(Y)N25/35CJXV1 / RYN35CJHXV1 Model R(Y)N25/35CJXV1 / RYN35CJHXV1 Model R(Y)N25/35CJXV1 / RYN35CJHXV1 Note: Dimension in mm Model: RN25/35FXV1 Model RN25/35FXV1 550 658 Note: Dimension in mm...
Service & Maintenance Service & Maintenance • Disconnect from main supply before servicing the air conditioner. • The unit is designed to give long life operation with minimum maintenance required. However, it should be regularly checked and the following items should be given due attention. Components Maintenance Procedures Period...
Service & Maintenance Pre Start Up Maintenance (After Extended Shutdown) Inspect thoroughly and clean indoor and outdoor units. Clean or replace air fi lters. Clean condensates drain line. Clean clogged indoor and outdoor coils. Check fan imbalance before operation. Tighten all wiring connections and panels. Check for refrigerant leakage.
Troubleshooting Troubleshooting Indicator Lights IR Signal Receiver When an infra red remote control operating signal has been transmitted, the signal receiver on the indoor unit will respond as below to confi rm acceptance of the signal transmission. ON to OFF 1 Long Beep OFF to ON 2 Short Beep...
Page 57
Troubleshooting LED Indoor Lights: Normal Operation and Fault Conditions for Cooling / Heatpump Unit Error Normal Operation / Action Code Fault Indication COOL/HEAT (GREEN/RED) Cool mode Green Heat mode Auto mode in Heating operation Auto mode in Cooling operation Green Time on Sleep mode on Fan mode on...
Troubleshooting LED Indicator Lights: Normal Operation and Fault Conditions for Cooling Unit FTN80F Operation / Fault Indication Action Power Timer Sleep Timer on Sleep mode on Dry mode Clean the fi lter and Frost prevention switch to high fan Room air sensor contact loose/ Call your dealer short 1 time...
Troubleshooting Phase Sequencer The unit with Scroll Compressor only can rotate in one direction. For this reason, a protective device (phase sequencer) is fi tted to prevent incorrect wiring of the electrical phases. When the three phases are not connected correctly, the phase sequencer operates, and the unit will not start. This device is located in the control box of the outdoor unit.
Troubleshooting Error Code / Fault Condition When a malfunction of the air conditioner unit is detected, immediately switch off the main power supply before proceeding with the following troubleshooting procedures. The following are common fault conditions and simple troubleshooting tips. If any other fault conditions which are not listed occur, contact your nearest local dealer.
Page 61
Troubleshooting Diagnostic Guidelines By means of pressure readings: Data Pressure Probable cause Circuit High side • 1. Overcharged with refrigerant. Low side • 2. Non-condensable gases in refrigerant circuit (e.g. air). 3. Obstructed air-intake / discharge. 4. Hot air short circuiting in outdoor unit. High side •...