Power Connections; Timing Connections - National Instruments VXI-MIO Series User Manual

Multifunction i/o modules for vxibus
Table of Contents

Advertisement

Power Connections

Warning: Under no circumstances should you connect these +5 V power pins directly

Timing Connections

Warning: Exceeding the maximum input voltage ratings, which are listed in
National Instruments Corporation
Figure 4-9 shows DIO<0, 2..3, 5..6> configured for digital input and
DIO<1, 4, 7> configured for digital output. Digital input applications
include receiving TTL signals and sensing external device states such
as the state of the switch. Digital output applications include sending
TTL signals and driving external devices such as the LED.
One pin on the I/O connector supplies +5 V from the VXIbus power
supply via a self-resetting fuse. The fuse will reset automatically after
you remove the overcurrent condition. These pins are referenced to
DGND and can be used to power external digital circuitry.
Power rating +4.65 to +5.25 VDC at 1 A
to analog or digital ground or to any other voltage source on the
VXI-MIO Series module or any other device. Doing so can damage the
VXI-MIO Series module and your device. National Instruments is
liable for damages resulting from such a connection.
Tables 4-1 and 4-2, can damage the VXI-MIO Series module. National
Instruments is
liable for any damages resulting from incorrect signal
NOT
connections.
All external control over the VXI-MIO module timing is routed through
the 10 programmable function input signals labeled PFI<0..9>. These
signals are explained in detail in the Programmable Function Input
Connections section in this chapter. These PFI signals are bidirectional;
as output signals they are not programmable and reflect the state of
many data acquisition, waveform generation, and general-purpose
timing signals. There are five other dedicated output lines for the
remainder of the timing signals. As input signals, the PFI signals are
programmable and can control any data acquisition, waveform
generation, and general-purpose timing signals.
The data acquisition signals are explained in the Data Acquisition
Timing Connections section later in this chapter. The waveform
generation signals are explained in the Waveform Generation Timing
4-23
Chapter 4
Signal Connections
NOT
VXI-MIO Series User Manual

Advertisement