Trial Operation

3. Trial Operation

Outline
1. Measure the power supply voltage and make sure that it falls within the specified range.
2. Trial operation should be carried out in either cooling or heating operation.
3. Carry out the trial operation in accordance with the operation manual to ensure that all
In cooling operation, select the lowest programmable temperature (18°C); in heating operation,
select the highest programmable temperature (30°C).
Detail
ARC466 Series
(1) Press the [On/Off] button to turn on the system.
(2) Press the center of the [Temp] button and the [Mode] button at the same time.
(3) Select T (trial operation) with the [Temp]
(4) Press the [Mode] button to start the trial operation.
(5) Press the [Mode] button and select operation mode.
(6) Trial operation terminates in approx. 30 minutes and switches into normal mode. To quit a
122
functions and parts, such as flap movement, are working properly.
The air conditioner requires a small amount of power in standby mode. If the system is not to
be used for some time after installation, shut off the circuit breaker to eliminate unnecessary
power consumption.
If the circuit breaker trips to shut off the power to the air conditioner, the system backs up the
operation mode. The system then restarts operation with the previous operation mode when
the circuit breaker is restored.
Trial operation may be disabled in either operation mode depending on the room
temperature.
After trial operation is complete, set the temperature to a normal level.
(26°C ~ 28°C in cooling, 20°C ~ 24°C in heating)
For protection, the system does not start for 3 minutes after it is turned off.
trial operation, press the [On/Off] button.