Thermistor Or Related Abnormality (Indoor Unit) - Daikin FVXG25K2V1B Service Manual

Inverter pair floor standing type
Hide thumbs Also See for FVXG25K2V1B:
Table of Contents

Advertisement

Troubleshooting
4.6

Thermistor or Related Abnormality (Indoor Unit)

C4 , C9 , CE
Error Code
Method of Error
The temperatures detected by the thermistors determine thermistor errors.
Detection
Error Decision
The thermistor input is more than 4.96 V or less than 0.04 V during compressor operation.
Conditions
Supposed
Causes
Troubleshooting
Check No.01
Refer to P.106
Check the connection of
connectors.
C4
C9
CE
70
Disconnection of connector
Defective thermistor
Defective indoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Normal?
YES
Check No. 01
Check the thermistor resistance
value.
Normal?
YES
: Indoor heat exchanger thermistor
: Room temperature thermistor
: Radiant panel thermistor
NO
NO
SiBE061121_A
Correct the connection.
Replace the thermistor.
Replace the indoor unit PCB.