Four Way Valve Performance Check; Inverter Units Refrigerant System Check - Daikin FVXG25K2V1B Service Manual

Inverter pair floor standing type
Hide thumbs Also See for FVXG25K2V1B:
Table of Contents

Advertisement

SiBE061121_A
5.5

Four Way Valve Performance Check

Check No.13
5.6

Inverter Units Refrigerant System Check

Check No.14
Service Diagnosis
Turn the power off and then on
again.
Start heating operation.
S80
voltage at 220 - 240
VAC with compressor
on? (Fig. 1)
YES
Disconnect the four way valve coil
from the connector and check the
continuity.
Four way
valve coil resistance at
1000 ~ 2000 Ω?
YES
(Fig. 1)
Voltage at S80
220 - 240 VAC
Compressor
ON
Refrigerant system check
Is the
discharge pipe
thermistor disconnected
from the holder?
NO
Check for refrigerant leakage.
See the service diagnosis on
refrigerant shortage (U0).
∗ Four way valve coil
Cooling / Dry : No continuity
Heating : Continuity
NO
NO
Time
(R11904)
YES
Check
Replace the outdoor unit
PCB.
Replace the four way valve
coil.
Replace the four way valve.
(R15737)
Reconnect the thermistor.
Replace the refrigerant.
(R15833)
109