10. Installation Instruction
10.1 Select the Best Location
10.1.1 Indoor Unit
•
There should not be any heat source or steam near
the unit.
•
There should not be any obstacles blocking the air
circulation.
•
A place where air circulation in the room is good.
•
A place where drainage can be easily done.
•
A place where noise prevention is taken into consideration.
•
Do not install the unit near the door way.
•
Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
•
Recommended installation height for indoor unit shall be at
least 2.5m.
10.1.2 Outdoor Unit
•
If an awning is built over the unit to prevent direct sunlight or
rain, be careful that heat radiation from the condenser is not
obstructed.
•
There should not be any animal or plant which could be
affected by hot air discharged.
•
Keep the spaces indicated by arrows from wall, ceiling, fence
or other obstacles.
•
Do not place any obstacles which may cause a short circuit of
the discharged air.
•
If piping length is over the rated length, additional refrigerant
should be added as shown in the table below:
Model
Piping size
Gas
Liquid
mm
mm
(inch)
(inch)
RE9NKE
9.52
6.35
(3/8")
(1/4")
RE12NKE
9.52
6.35
(3/8")
(1/4")
RE15NKE
12.7
6.35
(1/2")
(1/4")
Example: If the unit is installed at a 10m distance, the quantity of
additional refrigerant should be 60 g. ...... (10-7) m x 20g/m = 60 g
Rated
Max
Min
Max
Length
Elev-
Piping
Piping
(m)
ation
Length
Length
(m)
(m)
(m)
5
5
3
15
5
5
3
15
5
5
3
15
11.1.3 Indoor/Outdoor Unit
Additio-
Piping
nal
length for
Refriger
add
ant
gas(m)
(g/m)
20
7
20
7
*This illustration is for explanation purposes only.
20
7
The indoor unit will actually face a different way.
24