12. Operation Control

12.1 Basic Function

12.1.1 Internal Setting Temperature
Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting
processes. These shifting processes are depending on the air conditioner settings and the operation environment.
The final shifted value will be used as internal setting temperature and it is updated continuously whenever the
electrical power is supplied to the unit.
12.1.2 Cooling Operation
12.1.2.1
Thermostat control
• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5℃
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature >
Compressor OFF point.
12.1.3 Soft Dry Operation
12.1.3.1
Thermostat control (The same as Cooling mode)
12.1.4 Heating operation
12.1.4.1
Thermostat control
• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature > +2.0℃
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature<
Compressor OFF point.
12.1.5 Automatic Operation
• Once AUTO mode is selected, operation mode is determined by set temperature of remote control and indoor
intake temperature.
1st judgment
JUDGE CONDITION
If indoor intake temp – Remote control
temp setting ≥ +2
If -2 ≤ indoor intake temp. – Remote
control Temp. setting ≤ +2
If indoor intake temp. – Remote control
temp. setting < -2
Remote Control Setting Temp. (16℃~30℃)
Auto operation Mode Shifting
Setting Temperature Limit Checking( Min:16 ℃; Max.:30℃)
Outdoor Air Temperature Shifting
Setting Temperature Limit Checking( Min:16 ℃; Max.:33℃)
Internal Setting Temperature
REFERANCE MODE
Cool mode
Dry mode
Heat mode
33