4
cP/BP series

iNitial iNsPectioN

Be certain to inspect all cartons or crates on each
unit as received at the job site before signing the
freight bill. Verify that all items have been received
and that there are no visible damages; note any
shortages or damages on all copies of the freight
bill. In the event of damage or shortage, remember
that the purchaser is responsible for fi ling the
necessary claims with the carrier. Concealed
damages not discovered until after removing the
units from the packaging must be reported to the
carrier within 24 hours of receipt.

GeNeral descriPtioN

These Packaged System Heat Pumps provide the
best combination of performance and effi ciency
available. Safety devices are built into each unit to
provide the maximum system protection possible
when properly installed and maintained.
The CP/BP Water-to-Air Heat Pumps are
Underwriters Laboratories (UL) and (cUL) listed for
safety. The water-to-Air Heat Pumps are designed to
operate with entering fl uid temperature between
25°F to 80°F in the heating mode and between 50°F
to 110°F in the cooling mode. Effi ciencies and
capacities will vary as entering fl uid and return air
temperatures vary.
50°F Min. EWT for well water applications
suffi cient water fl ow to prevent freezing.
Antifreeze solution is required for all closed loop
applications where the fl uid temperature may drop
below 50°F. Cooling Tower/Boiler and Earth
Coupled (Geo Thermal) applications should have
suffi cient antifreeze solution to protect against
extreme conditions and equipment failure. Frozen
water coils are not covered under warranty.
This product should not be used for temporarily
heating/cooling during construction. Doing so
may affect the unit's warranty.

MoViNG aNd storaGe

If the equipment is not needed for immediate
installation upon its arrival at the job site, it should
be left in its shipping carton and stored in a clean,
6 720 220 045
dry area. Units must only be stored or moved in the
normal upright position as indicated by the "UP"
arrows on each carton at all times. If unit stacking is
required, stack units as follows: Vertical units less
than 6 tons, no more than two high; horizontal units
less than 6 tons, no more than three high. Do not
stack units larger than 6 tons.

saFety coNsideratioNs

Installation and servicing of this equipment can be
hazardous due to system pressure and electrical
components. Only trained and qualifi ed personnel
should install, repair, or service the equipment. Untrained
personnel can perform basic functions of maintenance
such as cleaning coils and replacing fi lters.
Caution
When working on equipment, always observe
precautions described in the literature, tags, and
labels attached to the unit. Follow all safety codes.
Wear safety glasses and work gloves. Use a
quenching cloth for brazing, and place a fi re
extinguisher close to the work area.
The blower motor should only be operated when a
duct is installed and secured to heat pump duct
collar in order to avoid possible injury.

locatioN

Locate the unit in an indoor area that allows easy
removal of the fi lter and access panels, and has
enough room for service personnel to perform
maintenance or repair. Provide suffi cient room to
make fl uid, electrical, and duct connection(s). If the
unit is located in a confi ned space such as a closet,
provisions must be made for return air to freely
enter the space. On horizontal units, allow
adequate room below the unit for a condensate
drain trap and do not locate the unit above supply
piping. These units are not approved for outdoor
installation; therefore, they must be installed inside
the structure being conditioned.
Do not locate units in areas that are subject to
freezing.
Subject to change without prior notice
initial inspection
Before performing service or maintenance
operations on the system, turn off main power to
the unit. Electrical shock could cause personal
injury or death.
Revised 05-12