Panasonic U-72MF2U9 Service Manual page 137

3way vrf system
Table of Contents

Advertisement

2. Detailed Settings Function
Item code
Item
Fan tap setting
(Fan tap change in order
to prevent drop in air
discharge caused by
filter installation)
Humidifier ON time
(ON time per 60
seconds)
Timer function change
prohibit
Smudging control
Setting the Flap
Separately
*Only for 4-Way
Cassette type
Setting the Flap
Separately
*Only for 4-Way
Cassette type
Setting the Flap
Separately
*Only for 4-Way
Cassette type
Setting the Flap
Separately
*Only for 4-Way
Cassette type
No.
DC fan tap operating
mode
0000
Standard
High ceiling use
0001
For low
static-pressure filter
High ceiling use
For low
0003
static-pressure filter
For air-blocking
material
For air-blocking
0006
material
0000
No humidifier output
0001
1 second
0002
2 seconds
0058
58 seconds
0059
59 seconds
0060
Continuously ON
0000
Function disabled
0001
Function enabled
0000
No smudging control
0000
Air discharge
port
0001
0002
Flap
0003
(adjustment for
up-down
0004
airflow direction)
0005
0006
Setting data
Flap position during operation
Without separate setting
Swing
Move to position 1 and stay
Move to position 2 and stay
Move to position 3 and stay
Move to position 4 and stay
Move to position 5 and stay
4 - 15
Remote Controller Functions
Setting data
Description
Purpose
Standard (setting at shipment)
High ceiling setting 1 (with standard panel)
Ultra long-life filter, oil guard panel, ammonia deodorizing
filter, optical regenerative deodorizing filter
High ceiling setting 2 (with standard panel)
(Antibacterial) high-performance filter (90%)
(Antibacterial) high-performance filter (65%)
Air-cleaning unit, air-cleaning unit + optical regenerative
deodorizing filter, deodorant (activated charcoal) filter
For 3-way discharge, when discharge duct is connected
For 2-way discharge
Flap 1
=90
Electrical
(Motor No. 4)
component
box
Flap 2
Flap 4
(Motor No. 2)
(Motor No. 3)
=91
=92
Flap 3
(Motor No. 1)
When the flap position is set to
4 or 5 and the unit is in the
cooling or dry mode, the flap
position is moved to 3 and the
operation is started.
NOTE
The flap swings during the
operation under "Setting the
Flap Separately".
At this time, the unselected flaps
are moved to the position 1 .
3WAY VRF SYSTEM
Flap position
1
2
3
4
5
=93
1
2
3
4
5
6
7
8
9