12.1.3 Cooling Operation

12.1.3.1

Thermostat control

Compressor is OFF when Water Outlet Temperature – Internal Water Setting Temperature > -1.5°C for
continuously 3 minutes.
Compressor is ON after waiting for 3 minutes, if the Water Outlet Temperature – Water Inlet Temperature
(temperature at thermostat OFF is triggered) >3°C.
12.1.3.2

Cool Mode Operation

1
3 ways valve control:
3 ways valve switch and fix to cooling side.
o
2
Heat pump operates follow normal cooling operation.
3
Back up heater DOES NOT operate during cool mode.
4
Solar 3 way valve operates follow solar operation specification.
5
2 ways valve control:
2 ways valve is closed.
o
Cool Mode Operation Time Chart
3 ways valve
On
Off
2 ways valve
Open
Close
Heat Pump
On
Off
Backup Heater
On
Off
Solar Request
On
Off
Solar 3 way valve
On
Off
W ater Outlet Temp
Tank Temp.
Mode On
Solar Off due to
tank > solar temp.
o
8.5
C
o
77
C
HeatPump
Thermo Off
41
o
16
C
o
70
C
HeatPump
Thermo On