Diagnosis display
Abnormality/Protection control
Outdoor air temperature sensor
F36
abnormality
Indoor water inlet temperature sensor
F37
abnormality
Outdoor discharge pipe temperature
F40
sensor abnormality
F41
PFC control
Outdoor heat exchanger temperature
F42
sensor abnormality
F43
Outdoor defrost sensor abnormality
Indoor water outlet temperature sensor
F45
abnormality
Outdoor Current Transformer open
F46
circuit
Outdoor EVA outlet temperature sensor
F48
abnormality
Outdoor bypass outlet temperature
F49
sensor abnormality
Cooling high pressure overload
F95
protection
Abnormality judgement
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
4 times occurrence within 10
minutes
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
—
Continue for 5 sec.
Continue for 5 sec.
—
88
Primary location to verify
Outdoor air temperature sensor
(defective or disconnected)
Water inlet temperature sensor
(defective or disconnected)
Outdoor discharge pipe temperature
sensor (defective or disconnected)
Voltage at PFC
Outdoor heat exchanger temperature
sensor (defective or disconnected)
Outdoor defrost sensor (defective or
disconnected)
Water outlet temperature sensor
(defective or disconnected)
Insufficient refrigerant
Outdoor PCB
Compressor low
Outdoor EVA outlet temperature sensor
(defective or disconnected)
Outdoor bypass outlet temperature
sensor (defective or disconnected)
Outdoor high pressure sensor
Water pump or water leakage
Clogged expansion valve or strainer
Excess refrigerant
Outdoor PCB