3.4 Operational anomalies with manual reset.

Code "E"
00
Flame presence inhibited
02
Ignition block
03, 05, 06,
Internal block (electronic)
07, 11, 13,
14, 15, 16,
17, 44, 60
04
Non-volatile block
12
Overtemperature safety thermostat intervention / 24 V fuse
opening
18
System delivery temperature too high
19
System return temperature too high
25
System delivery temperature increase too fast
28
Fan fault (no Hall signal)
29
Fan fault
30
Temperature difference between system delivery and return too
high
31
System delivery sensor fault (short-circuited)
32
System return sensor fault (short-circuited)
33
Domestic circuit sensor fault (short-circuited)
36
System delivery sensor fault (open)
37
System return sensor fault (open)
38
Domestic circuit sensor fault (open)
65
Fan fault (insufficient air delivery)
E.g. if these values are given on the display it
E
02
means the appliance is in ignition "block". To
eliminate the block press the RESET button
located on the boiler panel.
Description
Cure
Check detection electrode
Check electronic card
Check gas valve
Check electronic card
Check electronic card
Replace electronic card
Check cause of block
Check electronic card fuses
Check safety thermostat
Check water circulation in system
Check water circulation in system
Check water circulation in system
Check main exchanger
Check fan
Check fuse "F3"
Check electronic card
Check fan
Check fuse "F3"
Check electronic card
Check water circulation in system
Replace system delivery sensor
Replace system return sensor
Replace domestic circuit sensor
Replace system delivery sensor
Replace system return sensor
Replace domestic circuit sensor
Check fan operation