Installing "B23 " Type Single Boiler With Open Chamber And Forced Draught - Immergas VICTRIX 50 Instruction Booklet And Warning

Hide thumbs Also See for VICTRIX 50:
Table of Contents

Advertisement

1.10 Installing "B
" type single boiler with open
23
chamber and forced draught.
"VICTRIX 50" boilers leave the factory in "B
figuration (open chamber and forced draught).
Air is drawn directly from the place where the boiler is
installed, by means of special slots obtained in the back
of the appliance and fumes are exhausted into a single flue
or directly to the outside. In this configuration the boiler is
classified B
type
23
.
With this configuration:
- air is drawn directly from the place where the boiler is
installed;
- the fume exhaust must be connected to its own single flue
or ducted directly to the outside.
Ø 80 vertical kit.
Kit assembly: Fit the Ø 80 terminal (2) up to the stop on
the central hole of the boiler, making sure to fit the ring (1);
this will ensure hold and joining of the elements making
up the kit.
• Coupling of extension pipes and elbows. To install possible
coupling extensions with other elements of the fume ex-
haust system, proceed as follows: fit the male end (smooth)
of the pipe or elbow up to the stop on the female end (with
lip seals) of the previously fitted element; this will ensure
hold and correct joining of the elements.
• Extensions for vertical exhaust kit. e max. vertical
straight length (without bends) usable for Ø 80 exhaust
pipes is 30 metres.
e kit comprises:
1 - Ring (1)
1 - Exhaust terminal Ø 80 (2)
2
1
" type con-
23
Using the Ø 80 vertical terminal for direct fume exhaust, the
terminal must be shortened (see note below); even in this
case the fixing ring (1) must be inserted, fitting it up to the
stop on the boiler cover.
15