Westinghouse WBR 055 Manual page 23

Installation start-up maintenance parts gas fired boiler residential and commercial models
Table of Contents

Advertisement

Figure 11 - Standard Piping with Pumps and Indirect Priority
NOTES:
1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes.
2. All closely spaced tees shall be within 4 pipe diameters center to center spacing.
3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees.
4. The minimum pipe size for connecting an indirect water heater is 1"
5. The minimum pipe size for connecting a 55 or 80 model boiler - 1".
6. Circulators are shown with isolation flanges. The alternative is standard flanges with full port ball valves. Purge valves can be used with
circulator flanges as an alternative.
7. A mixing valve is recommended if the DHW temperature is set above the factory setting of 119
8. Piping shown is Standard.
9. Install a minimum of 12 diameters of straight pipe upstream of all circulators.
10. VERY IMPORTANT – Minimum flow rates outlined in this manual must be maintained through the heat exchanger to minimize short cycling.
The piping will not support the weight of the circulators. Refer to the circulator manufacturer's instructions to properly support
the circulator. Failure to comply with these instructions could result in property damage, severe personal injury, or death.
o
F.
WHL-016 Rev. 4.14.16
23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wbr 285Wbr 080Wbc 399Wbr 199Wbr 110Wbr 155

Table of Contents