Enabling Functioning Of The External Temperature Probe By The Remote Control - Biasi Inovia 25C ERP User Manual And Installation Instructions

Wall hung, fanflue, roomsealed, high efficiency gas boiler
Hide thumbs Also See for Inovia 25C ERP:
Table of Contents

Advertisement

both in domestic hot water mode and in
heating mode.
• Check the gas pressures and flow rates as
shown in section "GAS CONVERSION" to
page 78 of this booklet.
• Check that the condensate produced dur-
ing functioning fills the pipe and is regularly
drained in the draining plant pipe.
• Switch off the boiler by pressing the 14 (Fig.
7.11) key for 2 seconds until the
symbol appears on the LCD display (Fig.
7.10).
The boiler will now go through an ignition se-
quence and the burner will light.
If after four ignition attempts (about four min-
utes) the boiler does not function and a code
that precedes the letter E and the writing RE-
SET appear on the LCD display, it indicates
that the safety lock-out has stopped the boiler.
The display background flashes (Fig. 7.13).
Fig. 7.13
Press the reset key on the boiler control panel
15 (Fig. 7.11) to reset its functioning.
For the first lighting up and following mainte-
nance procedures for the gas supply, it may
be necessary to repeat the resetting operation
several times so as to remove the air present
in the pipework.
After five consecutive resetting attempts the
reset button is inhibited. To restore its func-
tion it is necessary to switch the boiler off and
on from the electrical mains, using the fused
spur isolation switch fitted adjacent to the ap-
pliance.
- 68 -
COMMISSIONING
7.10 Enabling functioning of the
Functioning with the external probe in the
boiler must be enabled if the remote control
(optional) is used.
Act on the programming of the REMOTE con-
trol to enable its functioning if the remote con-
trol (optional) is used.
• Press button
enter in
Fig. 7.14
Press buttons
to enter the transparent programming (Fig.
7.15).
Fig. 7.15
• Press buttons
"PM15" program that enables the external
probe (Fig. 7.16).
external temperature probe by
the remote control
for more than 3 seconds to
mode.
0
21
3
1
8
6
9
1 5
1
2
and
or
at the same time
to display the

Advertisement