See or change the start ('Start2') of the next comfort period.
See or change the next start / stop periods, if necessary.
The schedule has always two comfort periods a day. The start and stop times can be set in
half-hourly intervals (30 min.).
10
VI.KT.F2.02
© Danfoss 06/2008
DH-SMT/DK

Maintenance

2 sec.
Enter the maintenance menus.
Date - time
It is only necessary to set the correct date and time in connection with the first use of the
ECL Comfort 110 controller or after a power break of more than 36 hours (see the chapter
on
Adapting the ECL Comfort 110 controller).
Flow temp. (flow temperature control)
Temp. min. (flow temp. limit, min.)
Setting range
-20 ... 110 °C
Set the allowed min. flow temperature for your system. Adjust the factory setting, if
required.
Temp. max. (flow temp. limit, max.)
Setting range
10 ... 150 °C
Set the allowed max. flow temperature for your system. Adjust the factory setting, if
required.
The setting for 'Temp. max.' has higher priority than 'Temp. min.'.
VI.KT.F2.02
DH-SMT/DK
1000
2000
2177
Factory setting
10 °C
2178
Factory setting
90 °C
© Danfoss 06/2008
11