Service Mode Operation; Caution For Refrigerant Leaks - Daikin RZQ200C7Y1B Installation Manual

Hide thumbs Also See for RZQ200C7Y1B:
Table of Contents

Advertisement

Setting mode 2
The H1P LED is on.
Setting procedure
1
Push the
button according to the required function
BS2 SET
(A~E). The LED indication that matches the required function is
shown below in the field marked
Possible functions
A additional refrigerant charging operation.
B refrigerant recovery operation/vacuuming operation.
C low noise operation level setting (
D automatic low noise operation setting at nighttime.
E power consumption limitation setting (
A
B
C
D
E
2
When the
BS3 RETURN
defined.
3
Push the
button according to the required setting
BS2 SET
possibility as shown below in the field marked
3.1 Possible settings for function A and B are
(OFF).
ON
(1)
OFF
(1) This setting = factory setting
3.2 Possible settings for function C, D and E
For function C
only: the noise of level 3 < level 2 < level
(
L.N.O.P
)
1
1 (
).
For function D only: automatic low noise at nighttime level 3
1
< level 2 < level 1 (
).
For function E
(
DEMAND
)
3
< level 2 < level 3 (
).
1
(1)
2
3
(1) This setting = factory setting
4
Push the
button and the setting is defined.
BS3 RETURN
5
When the
BS3 RETURN
starts according to the setting.
Refer to the service manual for more details and for other settings.
RZQ200+250C7Y1B
Split system air conditioner
4PW34720-1G – 07.2010
:
L.N.O.P
) ( external).
DEMAND
) (external).
H1P H2P H3P H4P H5P H6P H7P
w x x x x x x
w x x x x x w
w x x x x w x
w x x x x w w
w x x x w w w
button is pushed, the current setting is
.
(ON) or
ON
H1P H2P H3P H4P H5P H6P H7P
w x x x x c x
w x x x x x c
only: the power consumption of level 1
H1P H2P H3P H4P H5P H6P H7P
w x x x x x c
w x x x x c x
w x x x c x x
button is pushed again, the operation
10. S
ERVICE MODE OPERATION
Vacuuming method
At the first installation, this vacuuming is not required. It is required
only for repair purposes.
1
When the unit is at standstill and under the setting mode 2, set
the required function B (refrigerant recovery operation/
vacuuming operation) to
-
After this is set, do not reset the setting mode 2 until the
vacuuming is finished.
-
The H1P LED is ON and the remote controller indicates
(test operation) and the operation will be prohibited.
2
Evacuate the system with a vacuum pump.
3
Press the
BS1 MODE
Refrigerant recovery operation method
by a refrigerant reclaimer
1
When the unit is at standstill and under the setting mode 2, set
the required function B (refrigerant recovery operation/
vacuuming operation) to
-
The indoor unit and the outdoor unit expansion valves will
fully open and some solenoid valves will be turned on.
-
The H1P LED is ON and the remote controller indicates
(test operation) and the operation will be prohibited.
2
Cut off the power supply to the indoor units that have separate
power supply and the outdoor unit with the circuit breaker. After
the power supply to one side is cut off, cut off the power supply
to
the
other
OFF
communication between the indoor and outdoor unit may
become abnormal and the expansion valves will be completely
closed again.
3
Recover the refrigerant by a refrigerant reclaimer. For details,
see the operation manual delivered with the refrigerant
reclaimer.
11. C
AUTION FOR REFRIGERANT LEAKS
(Points to note in connection with refrigerant leaks.)
When a unit is installed in a small room, it is necessary to
take measures so that the leaked refrigerant amount does
not exceed the limit even if it leaks. As for the measures to
prevent the leak from not exceeding the limit, please
consult with your distributor.
If the leaked amount exceeds the limit, it may cause an
oxygen deficiency accident.
Introduction
The installer and system specialist shall secure safety against
leakage according to local regulations or standards. The
following standards may be applicable if local regulations are
not available.
The air conditioning systems, uses R410A as refrigerant. R410A
itself is an entirely safe non-toxic, non-combustible refrigerant.
Nevertheless care must be taken to ensure that air conditioning
facilities are installed in a room which is sufficiently large. This
assures that the maximum concentration level of refrigerant gas is
not exceeded, in the unlikely event of major leak in the system and
this in accordance to the local applicable regulations and standards.
(ON).
ON
button and reset the setting mode 2.
(ON).
ON
side
within
10
minutes. Otherwise,
the
Installation manual
17