Service Mode Operation; Caution For Refrigerant Leaks - Daikin RZQ200B8W1B Installation Manual

Table of Contents

Advertisement

10. S
ERVICE MODE OPERATION
Vacuuming method
At the first installation, this vacuuming is not required. It is required
only for repair purposes.
1
When the unit is at standstill and under the setting mode 2, set
the required function B (refrigerant recovery operation/
vacuuming operation) to
-
After this is set, do not reset the setting mode 2 until the
vacuuming is finished.
-
The H1P led is ON and the remote controller indicates
(test operation) and the operation will be prohibited.
2
Evacuate the system with a vacuum pump.
3
Press the
button and reset the setting mode 2.
BS1 MODE
Refrigerant recovery operation method
by a refrigerant reclaimer
1
When the unit is at standstill and under the setting mode 2, set
the required function B (refrigerant recovery operation/
vacuuming operation) to
-
The indoor unit and the outdoor unit expansion valves will
fully open and some solenoid valves will be turned on.
-
The H1P led is ON and the remote controller indicates
(test operation) and the operation will be prohibited.
2
Cut off the power supply to the indoor units that have separate
power supply and the outdoor unit with the circuit breaker. After
the power supply to one side is cut off, cut off the power supply
to
the
other
side
within
communication between the indoor and outdoor unit may
become abnormal and the expansion valves will be completely
closed again.
3
Recover the refrigerant by a refrigerant reclaimer. For details,
see the operation manual delivered with the refrigerant
reclaimer.
11. C
AUTION FOR REFRIGERANT LEAKS
(Points to note in connection with refrigerant leaks.)
When a unit is installed in a small room, it is necessary to
take measures so that the leaked refrigerant amount does
not exceed the limit even if it leaks. As for the measures to
prevent the leak from not exceeding the limit, please
consult with your distributor.
If the leaked amount exceeds the limit, it may cause an
oxygen deficiency accident.
Introduction
The installer and system specialist shall secure safety against
leakage according to local regulations or standards. The
following standards may be applicable if local regulations are
not available.
The air conditioning systems, uses R410A as refrigerant. R410A
itself is an entirely safe non-toxic, non-combustible refrigerant.
Nevertheless care must be taken to ensure that air conditioning
facilities are installed in a room which is sufficiently large. This
assures that the maximum concentration level of refrigerant gas is
not exceeded, in the unlikely event of major leak in the system and
this in accordance to the local applicable regulations and standards.
Installation manual
17
(ON).
ON
(ON).
ON
10
minutes. Otherwise,
Maximum concentration level
The maximum charge of refrigerant and the calculation of the
maximum concentration of refrigerant is directly related to the
humanly occupied space in to which it could leak.
The unit of measurement of the concentration is kg/m
kg of the refrigerant gas in 1 m
Compliance to the local applicable regulations and standards for the
maximum allowable concentration level is required.
According to the appropriate European Standard, the maximum
allowed concentration level of refrigerant to a humanly space for
R410A is limited to 0.44 kg/m
1
direction of the refrigerant flow
2
room where refrigerant leak has occurred (outflow of all the refrigerant
from the system)
Pay special attention to places, such as a basements, etc. where
refrigerant can stay, since refrigerant is heavier than air.
the
Procedure for checking maximum concentration
Check the maximum concentration level in accordance with steps 1
to 4 below and take whatever action is necessary to comply.
1
Calculate the amount of refrigerant (kg) charged to each system
separately.
amount of
refrigerant in a
single unit system
(amount of
refrigerant with
which the system is
charged before
leaving the factory)
Where a single refrigerant facility is divided into
NOTE
2 entirely independent refrigerant systems, use the
amount of refrigerant with which each separate system
is charged.
3
volume of the occupied space).
3
.
1
+
=
additional charging
total amount of
amount (amount of
refrigerant (kg) in
refrigerant added
the system
locally in
accordance with the
length or diameter of
the refrigerant
piping)
Split system air conditioner
3
(the weight in
2
RZQ200+250B8W1B
4PW25544-1A