Note:
When converting from natural gas to LPG, an flue gas orifice plate must additionally be installed in the condensate pan
as follows. When converting from LPG to natural gas the flue gas restrictor must be removed.
This assembly step takes place before the installation of the mixer chamber and the complete assembly.
7)
After removing the upper casing cover, undo the self-
tapping screw at the balanced flue locking mechanism.
8)
Slide the balanced flue locking mechanism in the direction
of the arrow. Pull the flue pipe up out of the condensate pan.
Conversion type plate
Conversion sets for CGB-75/100 for conversion to other gas types: (Please state the corresponding part number when ordering)
Conversion to LPG P (G31)
* ID imprinted on gas restrictor
3062555_201507

Conversion to other gas types

(if required)
9)
10)
Part no. 86 12 714
Flue gas orifice plate
Place the flue gas orifice plate Ø 53 mm into the condensate
pan and insert the flue pipe again.
Note:
During conversion from LPG to natural gas, the
flue gas orifice plate must be removed. Fit the
mixing chamber as described under point 6).
Re-assemble in reverse order.
Updating the type plate
Cut out the relevant lines from the type plate supplied
and affix them over the relevant lines on the appliance
type plate.
Figure: Updating the type plate