Wolf CGB-75 Assembly And Operating Instructions Manual page 53

Gas condensing boiler
Table of Contents

Advertisement

Fault
Fault
code
34
CRC fault, BCC
35
BCC missing
36
CRC fault, BCC
37
Incorrect BCC
38
BCC no. invalid
39
BCC system error
41
Flow monitoring
43
Burner starts > 20 per
hour
50
Activation of boiler
coding card
52
Activation of boiler
coding card
60
Ionisation current
fluctuates
61
Ionisation current fails
LED constantly red
3062555_201507
Troubleshooting
Cause
Faulty boiler coding card
Boiler coding card was removed
Faulty boiler coding card
The boiler coding card is incompatible with the control
unit PCB
Faulty boiler coding card
Faulty boiler coding card
Return temperature > Flow + 25 K
Flow rate through the heat exchanger too low or,
in case of cascade, measuring point of the header
temperature unsuitable, or power consumption of the
calorifier charging too low.
The boiler coding card must be enabled
The boiler coding card must be enabled
The siphon is blocked, or the flue gas system is
blocked, severe storm
Poor gas quality, monitoring electrode faulty,
severe storm
Ionisation cable shorted out or
ionisation electrode earthed (casing)
Remedy
Replace boiler coding card
Fit the correct boiler coding card
Replace boiler coding card
Fit the correct boiler coding card
Replace boiler coding card
Replace boiler coding card
Vent heating system, check system pressure
Check heating circuit pump
Check the flow rate
Header sensor must measure the common
feed temperature of the cascade.
Press reset 2 x
Press reset 2 x
Clean siphon, check flue gas system,
check ventilation air, check monitoring
electrode
Check monitoring electrode and cable
Check ionisation cable and position of
electrode to burner. Press reset
53