Vent Piping Guidelines - Lennox ELITE EL195UHE Installation Instructions Manual

Upflow / horizontal air discharge
Hide thumbs Also See for ELITE EL195UHE:
Table of Contents

Advertisement

CHIMNEY
OR GAS
VENT
(Check sizing
for water
heater only)
FURNACE
(Replaced
by EL195)
If an EL195UHE furnace replaces a furnace which was
commonly vented with another gas appliance, the size of
the existing vent pipe for that gas appliance must be
checked. Without the heat of the original furnace flue prod­
ucts, the existing vent pipe is probably oversized for the
single water heater or other appliance. The vent should be
checked for proper draw with the remaining appliance.
FIGURE 21
Exhaust Piping (Figures 24 and 25)
Route piping to outside of structure. Continue with installa­
tion following instructions given in piping termination sec­
tion.
CAUTION
Do not discharge exhaust into an existing stack or
stack that also serves another gas appliance. If verti­
cal discharge through an existing unused stack is re­
quired, insert PVC pipe inside the stack until the end
is even with the top or outlet end of the metal stack.
CAUTION
The exhaust vent pipe operates under positive pres­
sure and must be completely sealed to prevent leak­
age of combustion products into the living space.

Vent Piping Guidelines

NOTE - Lennox has approved the use of DuraVent
factured vent pipe and terminations as an option to PVC.
®
When using the PolyPro
vent pipe requirements stated in the unit installation in­
struction – minimum & maximum vent lengths, termination
clearances, etc. – apply and must be followed. Follow the
instructions provided with PoyPro by DuraVent venting
system for assembly or if requirements are more restrict­
ive. The PolyPro by Duravent venting system must also fol­
low the uninsulated and unconditioned space criteria listed
in table 7.
REPLACING FURNACE THAT
WAS PART OF A COMMON
VENT SYSTEM
WATER
HEATER
OPENINGS
(To Adjacent
Room)
®
by DuraVent venting system the
The EL195UHE can be installed as either a Non-Direct
Vent or a Direct Vent gas central furnace.
NOTE - In Non‐Direct Vent installations, combustion air is
taken from indoors and flue gases are discharged out­
doors. In Direct Vent installations, combustion air is taken
from outdoors and flue gases are discharged outdoors.
Intake and exhaust pipe sizing -- Size pipe according to
tables 4 and
home. Table 4 lists the minimum vent pipe lengths per­
mitted. Table
Regardless of the diameter of pipe used, the standard roof
and wall terminations described in section Exhaust Piping
Terminations should be used. Exhaust vent termination
pipe is sized to optimize the velocity of the exhaust gas as it
exits the termination. Refer to table 8.
In some applications which permit the use of several differ­
ent sizes of vent pipe, a combination vent pipe may be
used. Contact Lennox' Application Department for assis­
tance in sizing vent pipe in these applications.
NOTE - The exhaust collar on all models is sized to accom­
modate 2" Schedule 40 vent pipe. In horizontal applica­
tions, any transition to exhaust pipe larger than 2" must be
made in vertical runs of the pipe. Therefore a 2" elbow must
be added before the pipe is transitioned to any size larger
than 2". This elbow must be added to the elbow count used
to determine acceptable vent lengths. Contact the Applica­
tion Department for more information concerning sizing of
vent systems which include multiple pipe sizes.
NOTE - All horizontal runs of exhaust pipe must slope back to­
ward unit. A minimum of 1/4" (6mm) drop for each 12" (305mm)
of horizontal run is mandatory for drainage.
NOTE - Exhaust pipe MUST be glued to furnace exhaust fittings.
manu­
NOTE - Exhaust piping should be checked carefully to make
sure there are no sags or low spots.
MINIMUM VENT PIPE LENGTHS
EL195UHE
MODEL
045, 070, 090, 110, 135
*Any approved termination may be added to the minimum length listed.
Page 17
. Count all elbows inside and outside the
5
lists the maximum pipe lengths permitted.
5
Exhaust Pipe
12" max
of straight pipe
Horizontal Application
FIGURE 22
TABLE 4
MIN. VENT LENGTH*
5 ft. plus 2 elbows or
10 ft. plus 1 elbow
12" Min.
15 ft. or