Lennox ELITE EL195UHE Installation Instructions Manual page 33

Upflow / horizontal air discharge
Hide thumbs Also See for ELITE EL195UHE:
Table of Contents

Advertisement

CONDENSATE TRAP LOCATIONS
(Unit shown in upflow position with remote trap)
Field ProvidedVent
Min. 1" Above Condensate
Drain Connection
1" Min.
2" Max.
*5' max.
PV C PipeOnly
Trap can be installed a
maximum 5' from furnace
*Piping from furnace must slope down a minimum of
1/4" per ft. toward trap.
FIGURE 46
EL195UHE With Evaporator
Coil Using A Separate Drain
(Trap at coil is optional)
Field Provided Vent
(1" min. 2" max. above
condensate connec­
tion)
Condensate
Drain Connection
FIGURE 47
T o Drai n
Evaporator drain
line required
Page 33
Condensate Trap With Optional Overflow Switch
From Evaporator Coil
Horizontal Furnace 4" Min. to 5" Max.above
Optional
FIGURE 48
condensatedrain connection)
Furnace Condensate