Lennox ELITE EL195UHE Installation Instructions Manual page 45

Upflow / horizontal air discharge
Hide thumbs Also See for ELITE EL195UHE:
Table of Contents

Advertisement

EL195
Gas
Unit
0-4500 ft.
Natural
All
Sizes
LP/propane
NOTE - A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion
procedure.
LP/Propane Conversion Kit and Pressure Switch Requirements at Varying Altitudes
Natural to
LP/Propane
EL195
Unit
0 - 7500 ft
(0 - 2286m)
-045
-070
-090
*69W73
-110
-135
* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit.
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-1370 m).
Manifold and Supply Line Pressure 0-10,000ft.
Manifold Pressure in. wg.
4501-5500 ft.
5501-6500 ft.
3.5
3.3
10.0
9.4
High Altitude
Natural Burner
Orifice Kit
7501 - 10,000 ft
(2286 - 3038m)
73W37
TABLE 14
6501 - 7500ft.
3.2
3.1
9.1
8.9
TABLE 15
High Altitude
LP/Propane Burner
Orifice Kit
7501 - 10,000 ft
(2286 - 3038m)
*68W68
Page 45
Supply Line
Pressure
in. w.g.
7501 - 10000ft.
0 - 10000 ft.
3.5
4.5
10.0
11.0
High Altitude Pressure Switch
4501 - 7500 ft
7501 -10,000 ft
(1373 - 2286m)
(2286 - 3048m)
No Change
93W87
93W93
93W86
93W92
93W86
93W93
93W86
93W92
93W86
13.0
13.0