Underwriters Laboratories Requirements - CADDX Ranger 8600E Installation Manual

Downloadable control communicator
Hide thumbs Also See for Ranger 8600E:
Table of Contents

Advertisement

LOCATION
PAGE
250
27
Reserved
251
27
Reserved
252
27
Auxiliary 3 Communicator Code
27
Auxiliary 3 Extended Communicator Code
253
254
27
User On Site Communicator Code
27
Cross Zoning Time (Minutes)
255
REMEMBER! AFTER ALL DATA HAS BEEN ENTERED, PRESS [9]-[2]-[0]-[#] TO STORE DATA IN EEPROM!
LOCATION
PAGE
256-263
27
Control Panel Access Code
264-271
27
Callback Phone Number - Digits 1 - 8
272-279
27
Callback Phone Number - Digits 9 - 16
280
27
Answering Machine Defeat
281
27
Local Programming Lockout
282
27
Control Panel Shutdown
INSTRUCTIONS FOR UNDERWRITERS LABORATORIES INSTALLATIONS
When installing a Ranger 8600E in compliance with UL-985 (Residential Fire) and UL-1023 (Residential Burglary)
the following instructions must be followed.
„The Ranger 8600E Control Panel and keypad must be mounted indoors and within the protected area.
„The rechargeable system battery should be replaced at no more than four-year intervals. The Ranger 8600E should
be tested annually with and without A.C. power. This will insure that the battery is connected and adequately charged
at the time of the test.
„All electrical wiring connected to the Ranger 8600E must be installed in accordance with the National Electrical Code,
ANSI and NFPA standards.
„When the built-in digital communicator is utilized in conjunction with a U.L. installation it must report at a minimum a
burglary zone, a fire zone, and A.C. power failure. The minimum number of dialing attempts programmed must be 5 if
one phone number is used and 3 if two phone numbers are used. The maximum number of dialing attempts
programmed must be 10 if one phone number is used and 5 if two phone numbers are used.
„Swinger shutdown feature must not be enabled.
„Control panel shutdown must not be enabled.
„U.L. has tested the Ranger 8600E to be compatible with the Silent Knight No. 9000 receiver.
„All interconnections to the Ranger 8600E must be made using U.L. labeled limited energy cable.
„Use Caddx Part #EOL-34UL for all U.L.985 installations.
„Force Arming and/or Automatic Arming shall not be enabled.
„ (1) For 24 hours of standby power using a 6.5 AH battery, limit auxiliary power load to 130 mA.
(2) For 24 hours of standby power using a 17.2 AH battery, limit auxiliary power load to 400 mA.
 Maximum exit delay time is 60 seconds. Maximum entry delay time is 45 seconds.
 Where cross zoning is employed, the cross-zones shall overlap 100% of the protection of the other zone. Volumetric
protection shall only be cross-zoned with other volumetric protection and perimeter protection shall only be cross zoned
with perimeter protection.
 The 8600E is compatible with the following 2-wire smoke detectors:
System Sensor Model 1151, 2100T, 2151, 2100; Sentrol Models 429AT, 521B, 521BXT; Hochiki Models SLK-835.
DESCRIPTION
DOWNLOADING ACCESSIBLE LOCATIONS
DESCRIPTION
DATA
31
DATA
DEFAULT
Reserved
Reserved
"0"
"0"
"0"
"5"
DEFAULT
"8 6 0 0 0 0 0 0"
"0" Disabled
"0" Disabled
"0" Disabled
"0" Not Locked