Your fireplace is approved to be vented either through
the side wall, or vertically through the roof.
Only MHSC venting components specifically ap-
proved and labelled for this fireplace may be used.
Vent terminations shall not be recessed into a wall or
siding.
Horizontal venting which incorporates the twist lock
pipe must be installed on a level plane without an
inclining or declining slope.
Horizontal venting which incorporates the use of flex
venting shall have an inclining slope from the unit of
1" (25 mm) per 24" (610 mm).
There must not be any obstruction such as bushes,
10007317

General Venting

garden sheds, fences, decks or utility buildings within
24" (610 mm) from the front of the termination hood.
Do not locate termination hood where excessive snow
or ice build up may occur. Be sure to check vent termi-
nation area after snow falls, and clear to prevent ac-
cidental blockage of venting system. When using snow
blowers, make sure snow is not directed towards vent
termination area.
Location of Vent Termination
It is imperative the vent termination be located observ-
ing the minimum clearances as shown on the next
page.
*Check with local codes or in absence of same with
CSAB149.1 Installation Codes (1991) for Canada or fol-
low the current National Fuel Gas Code, ANSI Z223.1/
NFPA 54 for installations in the USA.