Sharp AH-A07BE Service Manual page 19

Split system room air conditioners
Hide thumbs Also See for AH-A07BE:
Table of Contents

Advertisement

4. Hot-Keep
This function automatically controls the on-off operation
of the indoor fan motor in accordance during the
heating operation, thereby preventing the air conditioner
from delivering a cold air when the compressor is off.
When the room temperature exceeds the thermostat
line "H1", the compressor is turned off, and the indoor
fan motor is turned off after rotating at "HUL" for 30
seconds. 3 minutes and 10 seconds after turning off the
compressor, the indoor fan motor is turned on for 3
minutes and 20 seconds. At 10 seconds after turning
on the compressor, the indoor fan motor is turned on.
The next compressor OFF time is for 3, 8 or more than
8 minutes according to the room temperature (the time
increases with a rise of room temperature) when 3
minutes elapse after turning on the compessor.
3 min.
Compressor ON
OFF
ON
UL
Indoor
fan motor
OFF
30sec.
Thermo off
Figure Y-7
5. Preheat air flow
This function is intended to prevent cold air from being
discharged when the heating operation starts or when
defrosting.
When the indoor pipe temperature is below 29˚C at the
begining of the heat operation or after defrosting, the
indoor fan motor stays.
When the indoor pipe temperature gets higher than
29˚C, the fan motor is turned on at speed "HUL" after
compensation of starting.
When the indoor pipe temperature exceeds 35˚C, the
specified fan speed is restored. When the indoor pipe
temperature falls below 30˚C, the fan speed shifts
down to "HUL". And, when the indoor pipe temperature
falls below 23˚C, the fan motor turns off. Then, over
29˚C , it turns on again at speed "HUL".
35
30
29
24
OFF
UL
Figure Y-8
3 min.
UL
30sec.
10sec.
10sec.
time
Preset
OFF
UL
UL
Fan speed
6. Overheating protection system
When overloading occurs during the heating operation,
this system controls the outdoor fan motor according to
the indoor pipe temperature to prevent the overloading
of the compressor and restrain the rise in high pressure.
When the indoor pipe temperature exceeds U1˚C, the
outdoor fan motor is turned off, and when the indoor
pipe temperature falls U2˚C, the outdoor fan motor
turns on.
If 3 minutes elapse after turning off outdoor fan motor,
the outdoor fan motor is turned on, when the indoor
pipe falls U2' ˚C,
OFF
U1
U2'
U2
Within 3 minutes
Fan speed
MODELS
LIne
U1
AY-A07BE
U2'
AY-A07BE-C
U2
U2
AY-A09BE
U'2
AY-A09BE-C
U2
U2
AY-A12BE
U2'
U2
19
OFF
U1
ON
U2'
U2
Over 3 minutes
Figure Y-9
Table Y-3
HM
HH
HAH
HAL
HL
HUL
53˚C
53˚C
52˚C
52˚C
49˚C
49˚C
53˚C
54˚C
52˚C
53˚C
49˚C
50˚C
53˚C
54˚C
52˚C
53˚C
49˚C
50˚C
AH-A07BE-C/09BE-C
AH-A07BE/09BE/12BE
AY-A07BE-C/09BE-C
AY-A07BE/09BE/12BE