Empire Comfort Systems DV25IN33LN-3 Installation Instructions And Owner's Manual page 12

Direct vent gas fireplace heater
Table of Contents

Advertisement

GAS SUPPLY
NOTICE: The millivolt gas controls are equipped with a captured
screw type pressure test point, therefore it is not necessary to
provide a 1/8" test point up stream of the control.
When using copper or flex connector use only approved fittings.
The appliance and it's individual shut off valve must be disconnected
from supply piping system during any pressure testing of that system
at test pressures in excess of 1/2 psig (3.5kPa).
The appliance must be isolated from the gas supply piping system
by closing its individual manual shut off valve during any pressure
testing of the gas supply piping system at test pressures equal to
or less than 1/2 psig (3.5kPa).
Attention! If one of the procedures results in pressures in excess of
1/2 psig (14" w.c.) (3.5 kPa) on the fireplace gas valve, it will result
in a hazardous condition.
Checking Manifold Pressures
Both Propane and Natural gas valves have a built-in pressure
regulator in the gas valve. Natural gas models will have a manifold
pressure of approximately 3.5" w.c. (.871kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 4.5" w.c.
(1.120kPa) for the purpose of input adjustment to a maximum of
14.0" w.c. (3.484kPa). Propane gas models will have a manifold
pressure approximately 10.0" w.c. (2.49kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 10.8" w.c.
(2.68kPa) for the purpose of input adjustment to a maximum of
14.0" w.c. (3.484kPa).
Figure 6
Page 12
35657-4-1015

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents