Boiler/Group 2

"2" - select for constant temperature control units (see page 53).
Coding
Coding in the delivered condition
01:1
Do not adjust (only for
constant temperature
control units)
04:1
Minimum burner pause
subject to the boiler load
(specified by boiler cod-
ing card)
06:...
Maximum limit of the
boiler water temperature,
specified in °C by the
boiler coding card
0d:0
Do not adjust
0E:0
Do not adjust
13:1
Do not adjust
14:1
Do not adjust
15:1
Do not adjust
21:0
No service interval (hours
run) selected
23:0
No time interval for
burner service
24:0
No display "Service"
indication
28:0
No burner interval igni-
tion
2E:0
Do not adjust
(cont.)
Possible change
04:0
Minimum burner pause set
permanently (specified by
boiler coding card)
06:20
Maximum limit of the boiler
to
water temperature within
06:127
the ranges specified by the
boiler
21:1
The number of hours run
to
before the burner should
21:100
be serviced is adjustable
from 100 to 10 000 h
One adjusting step ≙
100 h
23:1
Interval adjustable from 1
to
to 24 months
23:24
24:1
Display "Service" indica-
tion (address is automati-
cally set and must be man-
ually reset after the serv-
ice)
28:1
Time interval adjustable
to
from 1 to 24 h. The burner
28:24
is force-started once every
30 s (only when operating
with LPG)
Code 2
63