Viessmann VITODENS 200-W Service Instructions Manual page 80

Table of Contents

Advertisement

Code 2
Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
E8:1
Minimum speed in opera-
tion with reduced room
temperature subject to
the setting in coding
address "E9" (only for
weather-compensated
control units)
E9:45
Speed of the variable
speed heating circuit
pump: 45 % of the maxi-
mum speed during oper-
ation with reduced room
temperature (only for
weather-compensated
control units)
F1:0
Screed drying function
disabled (only for
weather-compensated
control units)
F2:8
Time limit for party mode
or external heating pro-
gram changeover via key:
8 h (only for weather-
compensated control
units)
F5:12
Run-on time of the inter-
nal circulation pump in
heating mode: 12 min
(only for constant temper-
ature control units)
Party mode ends automatically in the "Heating and DHW" program, when the
*1
system changes over to operation with standard room temperature.
80
*1
Possible change
E8:0
Speed subject to the set-
ting in coding address
"E7"
E9:0
Speed adjustable from 0 to
to
100 % of the maximum
E9:100
speed during operation
with reduced room temper-
ature
F1:1
Screed drying function
to
adjustable in accordance
F1:6
with 6 optional tempera-
ture/time profiles (see
page 126)
F1:15
Constant flow temperature
20 °C
F2:0
No time limit for party
mode
F2:1
Time limit adjustable from 1
to
to 12 h
F2:12
F5:0
No run-on time for the inter-
nal circulation pump
F5:1
Run-on time of the internal
to
circulation pump adjusta-
F5:20
ble from 1 to 20 min
(cont.)
*1
*1