CONTINUED FRAMING AND INSTALLATION

FRAMING CONSTRUCTION INSTALLATION

1. The 80ZC cabinet is now ready for framing as follows:
a. Frame the 80ZC using 2" x 4" studs or local building code framing. Some minor framing
restrictions are required. For optional Mantel Height see page 23 figure 23.
b. Adjacent side walls must be at least 16" from the outer edge of the 80ZC trim panel.
(See Figure 17 )
NOTE: Maintain 2" clearance at the side walls and rear of the cabinet and any combustible
material (See Figure 17).
c. The overall opening dimensions must be at least 47 1/2" wide and 41 1/2" high.
d. 2" x 4" framing above the unit must be turned flat. This allows proper clearance from framing to
chimney (2" minimum). (See Page 19 Figure 18, Page 20 Figure 19)
Exterior Roof or Chase framing (Page 19).
Corner Location framing (Page 20).
CAUTION: Maintain a 2" air space between the rear and side of cabinet to
combustible materials.
MIN 2"
FIGURE 17
MIN 2"
Page 17
MIN 2"
MIN 16"