Trial Operation
How to check airflow direction
How to deactivate test operation
BRC7E830
182
Step
Action
8
Push Menu/OK button to enter Main Menu.
9
Use
buttons to select Airflow Direction
and push Menu/OK button.
10
Check that the airflow direction is actuated
according to the setting and push Menu/OK
button.
11
Press and hold Cancel button for 4 seconds to
enter Service Settings menu.
12
Use
buttons to select Test Operation in
the menu and push Menu/OK button.
Step
Action
1
Turn on the power supply more than 6 hours before test operation.
2
Open the gas stop valve.
3
Open the liquid stop valve.
4
Set to cooling operation with the remote controller and start operation by pressing ON/OFF
button.
5
Press INSPECTION/TEST button (
3 minutes.
6
Press SWING button to make sure the unit is in operation.
7
Press INSPECTION/TEST button (
8
Confirm all the function of unit according to the operation manual.
9
If the decoration panel has not been installed, turn off the power after the test operation.
Remote controller
) 2 times and operate at test operation mode for
/TEST
) and operate normally.
/TEST
Trial Operation and Field Settings
SiUS121602E
(R18829)
(R18830)
(R18827)