Remote Controller Thermistor Abnormality - Daikin CTXS07LVJU Service Manual

Hide thumbs Also See for CTXS07LVJU:
Table of Contents

Advertisement

Troubleshooting for FFQ Series
6.6

Remote Controller Thermistor Abnormality

CJ
Error Code
Method of Error
Even if remote controller thermistor is faulty, system is possible to operate by system thermistor.
Malfunction detection is carried out by the temperature detected by the remote controller
Detection
thermistor.
Error Decision
The remote controller thermistor is disconnected or shorted while the unit is running.
Conditions
Supposed
Causes
Troubleshooting
Note:
To delete the record of error codes, press ON/OFF button for 4 seconds or more while the error
code is displayed in the inspection mode.
130
Defective thermistor
Broken wire
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Delete the record of error
codes. (See the Note.)
CJ
Is
displayed on the
remote controller
again?
YES
NO
SiUS121602E
External factor other than
equipment malfunction.
(for example, noise etc.)
Replace the remote
controller.
Service Diagnosis
(R21111)