SECTION 6 • FAULT CODES

FAULT CODES

A fault code will appear in the control panel display if there
is a lockout failure. A letter and the number of the burner
module appear alternately in the display. Th e letter A is for
a lockout fault and E is for a blocking fault. Th e two right
segments show a fault code, table 2 gives the meaning
of the different codes. If there is a fault in more than one
burner module, the display alternates every 5 seconds
between burner modules and their associated fault codes.
MASTER BOARD BLOCKING CODES
E09
Control Error: Internal RAM location not correct
E12
Control Error: Th e incorrect parameters are
programmed in the slave board
E13
Control Error: A references measurement
indicated that the AD-circuit is defective, too low
E14
Control Error: A references measurement
indicated that the AD-circuit is defective, too
high
E15
Control Error: A references measurement
indicated that the AD-circuit is defective, too low
E16
Control Error: A references measurement
indicated that the AD-circuit is defective, too
high
E18
Control Error: Internal RAM
E19
Control Error: Not able to read parameters
E20
No slave board present
E22
Power Fault: Th e 50Hz has too large deviation
E60
Tank sensor opened circuit
E65
Return sensor opened circuit
E70
Tank sensor shorted
E75
Return sensor shorted
SLAVE BOARD BLOCKING CODES
E0
Read Error: Not able to read stored parameters
E28, E29, Control error: Reference measurements
E30, E31 indicates that there is an error in the AD circuit
E33
Flame detected when gas valve was closed
E41
Phase Error: Live and neutral reversed
E42
Phase Error: Too much deviation in the supply
voltage frequency
E44
Control Error: Poor communication between the
two processors
E47
Return sensor open circuit
E48
Flow sensor open circuit
E63
Return sensor short circuit
E64
Flow sensor short circuit
E78
Reset Error: Too many user resets
Lockout faults can be reset using the reset button. Only
the burner module for which the fault code appears in the
display at that moment is reset. Any E code (or blocking
fault) will require some form of rectifi cation before it can be
reset, i.e. repair or replacement of a component or part. An
E code could indicate a fault in connection with the Master
or Slave boards.
SLAVE BOARD LOCKOUT CODES
A01
A02
A03
A05
A06
A08
A09
A10
A11
A12
A14
A15
A16
A17
A19
A20
A21
A24
MAXXfl o Water Heater
Th ree Failed Ignitions: After three ignitions,
there was still no fl ame detected
Overheat Stat Failure: No water fl ow conditions,
the fl ow sensor is not detecting a temperature
increase during operation
Th e two fl ow sensors have too greater
temperature differential between them, 10°C for
more than 60 seconds
Gas Valve Relay Error: Th e gas valve relay is not
switching correctly
Safety Relay Error: Th e safety relay is not
switching correctly
Fan Error: Th e fan is not reaching its target value
or speed for more than 60 seconds
Control Error: Internal storage location
Th e contents of the stored parameters are not
correct
Flow Temperature: Flow temperature went above
95°C
Control Error: Th e stored contents inside the
control are not matching the software version
Control Error: Internal storage location
Control Error: Internal storage location
Control Error: Internal storage location
Control Error: Internal storage location
Control Error: Internal storage location
Flame detection after gas valve is closed. Flame
still present 10 seconds after the gas valve is
closed
Flame detected before opening of the gas valve
during the start up sequence
Too many fl ame failures: When the fl ame fails
three times within on burn cycle