Approved Vent Config's With A Vertical Termination And Two 90° Elbows - Travis Industries heritage bay Owner's Manual

Freestanding direct-vent
Hide thumbs Also See for heritage bay:
Table of Contents

Advertisement

S
TOVE
P
12
AGE
Approved Venting Configurations for Vertical Terminations with Two 90° Elbows
¥ The termination must fall within the shaded area shown in the chart. Use the indicated restrictor position.
35' (max)
(10.7 M)
(9.1 M)
(7.5 M)
20 feet
(4.6 M)
10 feet
(3 M)
8 feet (min.)
(2.4 M)
(1.5 M)
0 feet
I
NSTALLATION
Restrictor
Position # 3
30 feet
25 feet
(6 M)
15 feet
NOTE:
5 feet
Horizontal sections require a 1/4" (6 mm)
rise every 12" (300 mm) of travel.
Do not place an elbow directly off
the top of the heater.
(
.)
CONT
- For Qualified Installers Only!
NOTE:
Restrictor positions are based
upon lab tests. The ideal restrictor
position may vary slightly,
especially when the termination is
near a demarkation line.
35' (max)
(10.7 M)
30 feet
(9.1 M)
Restrictor
Position # 2
25 feet
(7.5 M)
20 feet
(6 M)
15 feet
(4.6 M)
Restrictor
10 feet
Position # 1
(3 M)
8 feet (min.)
(2.4 M)
5 feet
(1.5 M)
0 feet