accordance  with  the  cleanser/inhibitor  manufacturers'  instructions.  The  system  must  be  dosed 
to  the  concentrations  specified  by  the  inhibitor  manufacturer.  Inhibitor  concentrations  must  be 
monitored and maintained on an ongoing basis. Failure of components such as, but not limited 
to,  pumps,  auto  air  vents,  pressure  relief  valves  and  motorised  valves  due  to  corrosion  within 
the system will not be covered by warranty.
3.1.4 Air Vents
The plastic plug of the auto air vent factory­fitted to the appliance must be loosened when filling 
the system in order to bleed the air from the appliance. In addition to any factory fitted air vents 
it is recommended that another air vent is fitted at the highest point in the system. Where the 
flow  pipework  drops  down  from  the  appliance  the  installer  must  ensure  that  an  automatic  air 
vent is fitted to the top of the pipework to prevent air being trapped in the appliance.
3.1.5 Drain Cock
A  factory­fitted  drain  cock  is  fitted  to  the  return  pipe  of  the  appliance,  however  drain  cocks 
should  also  be  fitted  to  the  lowest  points  in  the  system  to  allow  the  system  to  be  completely 
drained.

3.1.6 Pipework

We strongly advise that all installation pipework is run in copper. However, if plastic pipe is used 
the  last  1000mm  of  pipework  connected  directly  to  the  appliance  must  be  of  copper.  All 
connections to the appliance must be made with compression fittings.
3.1.7 Heating System Design
The heating system must be designed for a fully pumped appliance.
3.2 Sealed Systems
3.2.1 Expansion Vessel
Refer  to  BS7074:  PART  1,  BS  EN  12828,  BS  EN  12831  and  BS  EN  14336  for  details  of 
expansion  vessel  sizing.  The  values  given  in  the  Table  4  below  are  for  total  system  volumes 
which include the water content of the appliance which can be found in Table 1: Product Data 
(See page 3). The WS18 appliance is supplied with an 18 litre expansion vessel charged to 1.0 
bar. This can accommodate a maximum combined appliance and system volume of 160 litres. If 
these maximum total system volumes are to be exceeded, additional expansion capacity will be 
required.  The WP18 appliance is not supplied with an expansion vessel and if connected to a 
sealed system, an expansion vessel must be fitted and sized according to Table 4 below.
INITIAL 
CHARGE 
(bar)
2.1
0.5
2.7
1.0
2.9
1.5
TOTAL 
SYSTEM 
25
VOLUME 
(Litres)
4.2
6.3
8.3
5.4
8.2
10.9
7.8
11.7
15.6
50
75
100
Table 4: Expansion Vessel Volumes.
VESSEL VOLUMES (Litres)
10.5
12.5
14.6
13.6
16.3
19.1
19.5
23.4
27.3
125
150
175
21
16.7
18.7
20.8
21.8
24.5
27.2
31.2
35.1
39.0
200
225
250
22.9
25.0
30.0
32.7
42.9
46.8
275
300