1-3. Other Component Specifications
Outdoor Units GRFP485L
MODEL No.
Outdoor Unit
Power Transformer
Rated
Primary
Secondary
Coil resistance
Thermal cut off temperature
Thermistor (Coil sensor) : TH7
Resistance
Thermistor (Discharge gas sensor) : TH8
Resistance
Relay (Comp. Magnetic Contactor)
Coil rated
Contact rating
Coil resistance (at 25°C)
Solenoid coil or 4 way valve
4 way valve
Solenoid coil
VAC, Hz
°C
KΩ
–10°C : 23.7 ± 5 %
– 5°C : 18.8 ± 5 %
0°C : 15.0 ± 5 %
5°C : 12.1 ± 5 %
10°C : 9.7 ± 5 %
KΩ
60°C : 13.8
70°C : 9.7
75°C : 8.2
80°C : 7.0
85°C : 5.9
VAC
VAC, A
_
1 - 53
GRFP485L
230 V, 50 Hz
14 V, 0.4A
WHT
WHT
: 300
BRN
BRN
: 2.2
PBC - 41E - S4
,
20°C : 6.5 ± 5 %
,
30°C : 4.4 ± 5 %
,
40°C : 3.1 ± 5 %
,
45°C : 2.6 ± 5 %
,
50°C : 2.1 ± 5 %
PTC - 51H - S1
,
90°C : 5.1
,
100°C : 3.8
,
110°C : 2.8
,
120°C : 2.2
,
130°C : 1.7