Technibel CAFP 124 R Technical Data & Service Manual page 48

Package air conditioner dc inverter r410a
Hide thumbs Also See for CAFP 124 R:
Table of Contents

Advertisement

1
1-3. Other Component Specifications
Ceiling-Mounted Type SPAFP
MODEL No.
Power Transformer
Rated
Primary
Secondary
Coil resistance
Thermal cut off temperature
Thermistor (Coil sensor) : TH
Resistance
Thermistor (Room sensor) :
Resistance
Electronic expansion valve
Valve body
Coil
Drain Pump
Rated
Float switch
Rated (Contact rated)
Indoor Unit
VAC, Hz
°C
KΩ
KΩ
SPAFP255-365-485R
–10°C : 23.7 ± 5 %
,
– 5°C : 18.8 ± 5 %
,
0°C : 15.0 ± 5 %
,
5°C : 12.1 ± 5 %
,
10°C : 9.7 ± 5 %
,
0°C : 16.5 ± 5 %
,
5°C : 12.8 ± 5 %
,
10°C : 10.0 ± 5 %
,
20°C : 6.3 ± 5 %
,
30°C : 4.0 ± 5 %
,
FS-0218-102
1 - 46
20°C : 6.5 ± 5 %
30°C : 4.4 ± 5 %
40°C : 3.1 ± 5 %
45°C : 2.6 ± 5 %
50°C : 2.1 ± 5 %
40°C : 2.7 ± 5 %
45°C : 2.2 ± 5 %
50°C : 1.8 ± 5 %
55°C : 1.5 ± 5 %