Technibel CAFP 124 R Technical Data & Service Manual page 54

Package air conditioner dc inverter r410a
Hide thumbs Also See for CAFP 124 R:
Table of Contents

Advertisement

1
1-3. Other Component Specifications
Outdoor Units GRFP365L
MODEL No.
Power Transformer
Rated
Primary
Secondary
Coil resistance
Thermal cut off temperature
Thermistor (Coil sensor) : TH7
Resistance
Thermistor (Discharge gas sensor) : TH8
Resistance
Relay (Comp. Magnetic Contactor)
Coil rated
Contact rating
Coil resistance (at 25°C)
Solenoid coil or 4 way valve
4 way valve
Solenoid coil
Outdoor Unit
VAC, Hz
°C
KΩ
KΩ
VAC
VAC, A
GRFP365L
230 V, 50 Hz
14 V, 0.4A
WHT
BRN
PBC - 41E - S4
–10°C : 23.7 ± 5 %
,
– 5°C : 18.8 ± 5 %
,
0°C : 15.0 ± 5 %
,
5°C : 12.1 ± 5 %
,
10°C : 9.7 ± 5 %
,
PTC - 51H - S1
60°C : 13.8
,
70°C : 9.7
,
75°C : 8.2
,
80°C : 7.0
,
85°C : 5.9
,
1 - 52
WHT
: 300
BRN
: 2.2
20°C : 6.5 ± 5 %
30°C : 4.4 ± 5 %
40°C : 3.1 ± 5 %
45°C : 2.6 ± 5 %
50°C : 2.1 ± 5 %
90°C : 5.1
100°C : 3.8
110°C : 2.8
120°C : 2.2
130°C : 1.7

Hide quick links: